Backflow assembly test · 266 Turkey Hill Ln
ApprovedFiled May 22, 2025 by Logan Danner, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- May 22, 2025
- Assembly type
- PVB
- Serial number
- A571981
- Size
- 1
- Test gauge serial
- G-4465
- Gauge calibration date
- Oct 24, 2024
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-71-01142
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.