← Backflow review queue
Backflow assembly test · 7464 Turkey Hill Ct
ApprovedFiled Jun 26, 2025 by Drew Ramirez, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Jun 26, 2025
- Assembly type
- PVB
- Serial number
- B210077
- Size
- 3/4
- Test gauge serial
- G-6953
- Gauge calibration date
- Apr 8, 2025
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-53-01125
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7464 Turkey Hill Ct
Owner: Rowan Ellery
Parcel 085-53-01125