Backflow assembly test · 1949 Sycamore Ct

Approved

Filed Jul 28, 2025 by Sam Benton, Summit Backflow Testing · filed from phone

Report

Date of service
Jul 28, 2025
Assembly type
RP
Serial number
K999393
Size
1
Test gauge serial
G-8344
Gauge calibration date
Jun 18, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 093-83-01090
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.