Solano County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Grill

Approved

Filed Nov 26, 2025 by Quinn Ashby, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Nov 26, 2025
Assembly type
RP
Serial number
K199949
Size
2
Test gauge serial
G-8864
Gauge calibration date
May 6, 2025
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 095-97-01161
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2621 Laurel Way
Owner: Nguyen Holdings LLC
Parcel 095-97-01161