Solano County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Medical Offices

Approved

Filed May 16, 2024 by Rowan Danner, Keystone Backflow Testing · filed from phone

Report

Date of service
May 16, 2024
Assembly type
DC
Serial number
K105063
Size
4
Test gauge serial
G-2880
Gauge calibration date
Apr 30, 2023
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
2.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 095-48-01106
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5906 Sycamore Dr
Owner: Ashby Holdings LLC
Parcel 095-48-01106