Backflow assembly test · 2121 Orchard Way
ApprovedFiled Oct 4, 2023 by Morgan Benton, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Oct 4, 2023
- Assembly type
- DC
- Serial number
- K975437
- Size
- 3/4
- Test gauge serial
- G-8027
- Gauge calibration date
- Jan 1, 2023
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 095-77-01011
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.