Solano County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Elementary School

Approved

Filed Sep 29, 2025 by Quinn Ashby, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Sep 29, 2025
Assembly type
RP
Serial number
W967874
Size
4
Test gauge serial
G-5509
Gauge calibration date
Aug 15, 2025
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 095-72-01073
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6362 Spring Branch Dr
Owner: Lindqvist Holdings LLC
Parcel 095-72-01073