← Backflow review queue
Backflow assembly test · Golden Taqueria
ApprovedFiled Dec 8, 2023 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 8, 2023
- Assembly type
- DC
- Serial number
- Z847288
- Size
- 1
- Test gauge serial
- G-6431
- Gauge calibration date
- Mar 5, 2023
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-51-01313
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1239 Quarry Trl
Owner: Okafor Holdings LLC
Parcel 097-51-01313