Backflow assembly test · Station Animal Hospital
ApprovedFiled Aug 18, 2026 by Taylor Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Aug 18, 2026
- Assembly type
- RP
- Serial number
- W894095
- Size
- 2
- Test gauge serial
- G-4853
- Gauge calibration date
- May 14, 2026
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-53-01244
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
8998 Laurel Rd
Owner: Calloway Holdings LLC
Parcel 097-53-01244