Backflow assembly test · Crossroads Apartments
ApprovedFiled May 21, 2024 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- May 21, 2024
- Assembly type
- DC
- Serial number
- A677924
- Size
- 2
- Test gauge serial
- G-7906
- Gauge calibration date
- Jan 22, 2023
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-81-01089
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.