Backflow assembly test · 4601 Sycamore Rd
ApprovedFiled Mar 15, 2026 by Taylor Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Mar 15, 2026
- Assembly type
- RP
- Serial number
- B668337
- Size
- 3/4
- Test gauge serial
- G-4527
- Gauge calibration date
- Feb 1, 2026
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-14-01007
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4601 Sycamore Rd
Owner: Avery Whitcomb
Parcel 097-14-01007