ApprovedFiled Aug 30, 2025 by Taylor Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Aug 30, 2025
- Assembly type
- RP
- Serial number
- K370660
- Size
- 3/4
- Test gauge serial
- G-4560
- Gauge calibration date
- Sep 5, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-90-01332
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.