Sonoma County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1662 Cedar Hollow Ln

Approved

Filed Mar 5, 2026 by Alex Kessler, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Mar 5, 2026
Assembly type
RP
Serial number
B105773
Size
1
Test gauge serial
G-3140
Gauge calibration date
Aug 5, 2025
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 097-12-01187
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1662 Cedar Hollow Ln
Owner: Casey Nguyen
Parcel 097-12-01187