Back to the backflow review queue

Backflow assembly test: Two Rivers Animal Hospital

Approved

Filed Jan 3, 2025 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 3, 2025
Assembly type
RP
Serial number
B969517
Size
2
Test gauge serial
G-1241
Gauge calibration date
Dec 1, 2024
Check valve 1
0.9 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Relief valve opened at
4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-65-01239
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2124 Cedar Hollow Ct
Owner: Benton Holdings LLC
Parcel 107-65-01239