Backflow assembly test · Blue Heron Animal Hospital
ApprovedFiled Dec 30, 2023 by Parker Vance, Summit Backflow Testing · filed from phone
Report
- Date of service
- Dec 30, 2023
- Assembly type
- RP
- Serial number
- Z580768
- Size
- 4
- Test gauge serial
- G-6853
- Gauge calibration date
- Mar 21, 2023
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-75-01223
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
401 Old Church Way
Owner: Ellery Holdings LLC
Parcel 107-75-01223