← Backflow review queue
Backflow assembly test · 3163 Orchard Way
ApprovedFiled May 7, 2026 by Shawn Stroud, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- May 7, 2026
- Assembly type
- RP
- Serial number
- B478069
- Size
- 1
- Test gauge serial
- G-8263
- Gauge calibration date
- Aug 2, 2025
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-21-01303
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3163 Orchard Way
Owner: Emerson Wexler
Parcel 111-21-01303