Backflow assembly test · 8824 Cedar Hollow Way
ApprovedFiled Apr 19, 2025 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Apr 19, 2025
- Assembly type
- RP
- Serial number
- B588703
- Size
- 1
- Test gauge serial
- G-2447
- Gauge calibration date
- Feb 9, 2025
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-65-01272
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.