Backflow assembly test · 166 Ridgeview Dr
ApprovedFiled Dec 9, 2025 by Emerson Wexler, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 9, 2025
- Assembly type
- DC
- Serial number
- A272293
- Size
- 3/4
- Test gauge serial
- G-2797
- Gauge calibration date
- Apr 14, 2025
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-31-01285
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.