Backflow assembly test · 2196 Laurel Rd
ApprovedFiled Jul 28, 2026 by Cameron Whitcomb, Evergreen Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 28, 2026
- Assembly type
- DC
- Serial number
- A933397
- Size
- 1
- Test gauge serial
- G-3504
- Gauge calibration date
- Mar 22, 2025
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-72-01337
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.