← Backflow review queue
Backflow assembly test · 2325 Stone Gate Trl
ApprovedFiled Mar 17, 2026 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Mar 17, 2026
- Assembly type
- DC
- Serial number
- Z148342
- Size
- 1
- Test gauge serial
- G-4333
- Gauge calibration date
- Nov 13, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-71-01068
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2325 Stone Gate Trl
Owner: Emerson Vance
Parcel 111-71-01068