Backflow assembly test · 6820 Hickory Rd
ApprovedFiled Oct 30, 2026 by Emerson Wexler, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 30, 2026
- Assembly type
- RP
- Serial number
- B300381
- Size
- 3/4
- Test gauge serial
- G-9228
- Gauge calibration date
- Apr 24, 2026
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-97-01051
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6820 Hickory Rd
Owner: Blake Danner
Parcel 111-97-01051