Backflow assembly test · 7122 Ridgeview Trl
ApprovedFiled Dec 30, 2024 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Dec 30, 2024
- Assembly type
- RP
- Serial number
- B807903
- Size
- 1
- Test gauge serial
- G-7949
- Gauge calibration date
- Dec 7, 2023
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 1.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-77-01220
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7122 Ridgeview Trl
Owner: Shawn Ramirez
Parcel 111-77-01220