Backflow assembly test · 1527 Spring Branch Ln
ApprovedFiled Apr 21, 2026 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Apr 21, 2026
- Assembly type
- RP
- Serial number
- B457279
- Size
- 1
- Test gauge serial
- G-7715
- Gauge calibration date
- Jul 18, 2025
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-33-01225
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1527 Spring Branch Ln
Owner: Avery Kessler
Parcel 111-33-01225