Backflow assembly test · 5739 Cedar Hollow Rd
ApprovedFiled Jun 24, 2025 by Rowan Harlow, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Jun 24, 2025
- Assembly type
- PVB
- Serial number
- Z719218
- Size
- 3/4
- Test gauge serial
- G-3131
- Gauge calibration date
- Oct 15, 2024
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Harlow, current on the service date
- All required fields present
- Address matches parcel 113-54-01175
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.