Backflow assembly test · 4284 Pine Knoll Dr
ApprovedFiled Dec 11, 2024 by Jordan Harlow, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 11, 2024
- Assembly type
- RP
- Serial number
- B580256
- Size
- 1
- Test gauge serial
- G-4552
- Gauge calibration date
- Mar 29, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Harlow, current on the service date
- All required fields present
- Address matches parcel 113-90-01128
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4284 Pine Knoll Dr
Owner: Parker Fairley
Parcel 113-90-01128