← Backflow review queue
Backflow assembly test · 5458 Mill Creek Way
ApprovedFiled Dec 12, 2023 by Rowan Harlow, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Dec 12, 2023
- Assembly type
- PVB
- Serial number
- W397616
- Size
- 3/4
- Test gauge serial
- G-7105
- Gauge calibration date
- Jun 26, 2023
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-17-01351
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5458 Mill Creek Way
Owner: Alex Benton
Parcel 113-17-01351