Backflow assembly test · Main Street Dental
ApprovedFiled Dec 28, 2025 by Casey Ramirez, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 28, 2025
- Assembly type
- DC
- Serial number
- Z762261
- Size
- 2
- Test gauge serial
- G-1055
- Gauge calibration date
- Jan 30, 2025
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Ramirez, current on the service date
- All required fields present
- Address matches parcel 113-14-01337
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.