Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7513 Meadow Lark Ln

Approved

Filed Mar 21, 2026 by Logan Ramirez, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Mar 21, 2026
Assembly type
RP
Serial number
K751973
Size
3/4
Test gauge serial
G-1711
Gauge calibration date
Oct 27, 2025
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-86-01338
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7513 Meadow Lark Ln
Owner: Casey Vance
Parcel 001-86-01338