← Backflow review queue
Backflow assembly test · Two Rivers Elementary School
ApprovedFiled Apr 18, 2025 by Reese Harlow, Clearwater Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Apr 18, 2025
- Assembly type
- RP
- Serial number
- B576249
- Size
- 2
- Test gauge serial
- G-1989
- Gauge calibration date
- Jun 24, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-21-01141
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.