Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Medical Offices

Approved

Filed Mar 30, 2026 by Logan Ramirez, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Mar 30, 2026
Assembly type
RP
Serial number
Z873543
Size
4
Test gauge serial
G-1438
Gauge calibration date
Aug 1, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-40-01308
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2256 Sycamore Dr
Owner: Ashby Holdings LLC
Parcel 001-40-01308