← Backflow review queue
Backflow assembly test · 8525 Stone Gate Way
ApprovedFiled Nov 18, 2023 by Rowan Marsh, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Nov 18, 2023
- Assembly type
- RP
- Serial number
- K764978
- Size
- 1
- Test gauge serial
- G-7288
- Gauge calibration date
- Nov 24, 2022
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-23-01150
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8525 Stone Gate Way
Owner: Logan Fairley
Parcel 001-23-01150