Backflow assembly test · 3826 Stone Gate Rd
ApprovedFiled Mar 18, 2026 by Quinn Wexler, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 18, 2026
- Assembly type
- PVB
- Serial number
- W653456
- Size
- 1
- Test gauge serial
- G-7355
- Gauge calibration date
- Nov 7, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-18-01271
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.