Backflow assembly test · 7339 Meadow Lark Dr

Approved

Filed Jul 2, 2025 by Casey Kessler, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Jul 2, 2025
Assembly type
DC
Serial number
K413790
Size
1
Test gauge serial
G-8995
Gauge calibration date
Apr 7, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-45-01085
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7339 Meadow Lark Dr
Owner: Cameron Kessler
Parcel 005-45-01085