Backflow assembly test · 7411 Spring Branch Trl

Approved

Filed Sep 22, 2024 by Cameron Kessler, Heritage Backflow Testing · filed from phone

Report

Date of service
Sep 22, 2024
Assembly type
RP
Serial number
W612846
Size
1
Test gauge serial
G-3134
Gauge calibration date
May 25, 2024
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-57-01223
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.