← Backflow review queue
Backflow assembly test · 7474 Pine Knoll Way
ApprovedFiled Jul 16, 2026 by Quinn Harlow, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 16, 2026
- Assembly type
- DC
- Serial number
- Z142627
- Size
- 3/4
- Test gauge serial
- G-7598
- Gauge calibration date
- May 29, 2026
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-34-01259
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7474 Pine Knoll Way
Owner: Quinn Wexler
Parcel 005-34-01259