Backflow assembly test · Two Rivers Market
ApprovedFiled Sep 6, 2024 by Morgan Wexler, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 6, 2024
- Assembly type
- RP
- Serial number
- Z204792
- Size
- 2
- Test gauge serial
- G-7312
- Gauge calibration date
- Jul 9, 2024
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-69-01056
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.