Arapahoe County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Elementary School

Approved

Filed Jul 25, 2026 by Quinn Harlow, Heritage Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jul 25, 2026
Assembly type
DC
Serial number
Z410155
Size
2
Test gauge serial
G-5651
Gauge calibration date
Oct 26, 2025
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-40-01265
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1165 Quarry Dr
Owner: Stroud Holdings LLC
Parcel 005-40-01265