Backflow assembly test · Two Rivers Grill
ApprovedFiled Nov 19, 2025 by Morgan Wexler, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 19, 2025
- Assembly type
- RP
- Serial number
- A635465
- Size
- 1 1/2
- Test gauge serial
- G-6891
- Gauge calibration date
- Jul 22, 2025
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Wexler, current on the service date
- All required fields present
- Address matches parcel 005-75-01313
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2782 Spring Branch Way
Owner: Kessler Holdings LLC
Parcel 005-75-01313