Arapahoe County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6566 Pine Knoll Rd

Approved

Filed Dec 4, 2025 by Cameron Kessler, Heritage Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Dec 4, 2025
Assembly type
RP
Serial number
Z532697
Size
3/4
Test gauge serial
G-5857
Gauge calibration date
Aug 25, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-38-01127
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6566 Pine Knoll Rd
Owner: Rowan Harlow
Parcel 005-38-01127