Backflow assembly test · 5156 Stone Gate Way

Approved

Filed Aug 2, 2026 by Cameron Kessler, Heritage Backflow Testing · filed from phone

Report

Date of service
Aug 2, 2026
Assembly type
RP
Serial number
Z765504
Size
1
Test gauge serial
G-7703
Gauge calibration date
Feb 9, 2026
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 005-37-01123
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5156 Stone Gate Way
Owner: Avery Stroud
Parcel 005-37-01123