Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8023 Laurel Rd

Approved

Filed Dec 12, 2025 by Drew Fairley, Evergreen Backflow Testing · filed from phone

Report

Date of service
Dec 12, 2025
Assembly type
RP
Serial number
A999924
Size
3/4
Test gauge serial
G-6142
Gauge calibration date
Sep 23, 2025
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-53-01284
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

8023 Laurel Rd
Owner: Cameron Ramirez
Parcel 013-53-01284