Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Pizza

Approved

Filed Jul 25, 2024 by Drew Fairley, Evergreen Backflow Testing · filed from phone

Report

Date of service
Jul 25, 2024
Assembly type
RP
Serial number
A392008
Size
1
Test gauge serial
G-3270
Gauge calibration date
Jan 13, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-90-01107
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5104 Hickory Way
Owner: Lindqvist Holdings LLC
Parcel 013-90-01107