Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4327 Cedar Hollow Rd

Approved

Filed Oct 28, 2025 by Casey Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Oct 28, 2025
Assembly type
RP
Serial number
Z987557
Size
1
Test gauge serial
G-2325
Gauge calibration date
May 3, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-31-01085
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4327 Cedar Hollow Rd
Owner: Emerson Benton
Parcel 013-31-01085