Backflow assembly test · 3404 Pine Knoll Ln
ApprovedFiled Oct 18, 2023 by Casey Kessler, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Oct 18, 2023
- Assembly type
- RP
- Serial number
- K785094
- Size
- 1
- Test gauge serial
- G-2243
- Gauge calibration date
- Aug 13, 2022
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-51-01355
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3404 Pine Knoll Ln
Owner: Hayden Marsh
Parcel 013-51-01355