← Backflow review queue
Backflow assembly test · 880 Turkey Hill Trl
ApprovedFiled Jun 11, 2024 by Cameron Kessler, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Jun 11, 2024
- Assembly type
- RP
- Serial number
- W417511
- Size
- 3/4
- Test gauge serial
- G-8199
- Gauge calibration date
- Aug 17, 2023
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-13-01248
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
880 Turkey Hill Trl
Owner: Casey Ellery
Parcel 013-13-01248