Backflow assembly test · 4318 Meadow Lark Way

Approved

Filed Jun 26, 2025 by Drew Fairley, Evergreen Backflow Testing · filed from phone

Report

Date of service
Jun 26, 2025
Assembly type
RP
Serial number
A144215
Size
1
Test gauge serial
G-6374
Gauge calibration date
Apr 2, 2025
Check valve 1
0 psid
Check valve 1 closed tight
No
Check valve 2
3.7 psid
Relief valve opened at
3.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-44-01275
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4318 Meadow Lark Way
Owner: Casey Vance
Parcel 013-44-01275