Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Diner

Approved

Filed Oct 25, 2025 by Casey Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Oct 25, 2025
Assembly type
RP
Serial number
A652386
Size
4
Test gauge serial
G-6339
Gauge calibration date
Jul 25, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-18-01335
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

5470 Quarry Ct
Owner: Nguyen Holdings LLC
Parcel 013-18-01335