Backflow assembly test · 6217 Cedar Hollow Rd

Approved

Filed Nov 25, 2024 by Cameron Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Nov 25, 2024
Assembly type
DC
Serial number
W545000
Size
1
Test gauge serial
G-6698
Gauge calibration date
Nov 15, 2023
Check valve 1
0.9 psid
Check valve 1 closed tight
No
Check valve 2
1.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-14-01243
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6217 Cedar Hollow Rd
Owner: Sam Fairley
Parcel 013-14-01243