Backflow assembly test · Hilltop Grill

Approved

Filed Aug 17, 2025 by Cameron Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Aug 17, 2025
Assembly type
RP
Serial number
K839582
Size
1 1/2
Test gauge serial
G-4069
Gauge calibration date
Oct 28, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-17-01184
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.