Backflow assembly test · 3177 Stone Gate Way

Approved

Filed May 28, 2025 by Drew Fairley, Evergreen Backflow Testing · filed from phone

Report

Date of service
May 28, 2025
Assembly type
DC
Serial number
A365193
Size
3/4
Test gauge serial
G-2051
Gauge calibration date
Apr 4, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-43-01210
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.